Wire & Cable
Compounds and additives for cable insulation, sheathing and fire performance — from commodity polyethylene jacketing to halogen-free systems for tunnels and rolling stock.

Which materials decide how a cable performs?
A cable is a stack of material decisions. The insulation sets the temperature rating and the dielectric behaviour. The sheath takes the mechanical and environmental punishment. The flame-retardant system determines what happens in a fire — and increasingly, what the cable is permitted to be used for at all. Each layer is a different compound with a different specification, and changing one usually has consequences for the others.
Revona Chemicals supplies the compounds and the additives behind those layers, from commodity polyethylene jacketing through to halogen-free systems for enclosed public spaces.
What insulation material fits which temperature rating?
The conductor temperature rating is usually the first constraint, because it determines how much current a given cross-section can carry. Thermoplastic PVC and polyethylene insulation is generally rated to 70 °C. Crosslinking lifts that to 90 °C: our silane-crosslinkable XLPE compound cures with moisture after extrusion, so a low-voltage line can produce 90 °C-rated cable without the curing tube that peroxide systems require.
Where 105 °C continuous service is specified, the limiting factor is usually not the polymer but the plasticiser leaving it. TOTM is the standard answer: a trimellitate molecule large enough that it stays in the compound over the cable's service life, where a general-purpose plasticiser would migrate out and leave the insulation hard and cracked.
Which compounds suit halogen-free and LSZH cable?
Cable for tunnels, metro systems, rolling stock, data centres and high-occupancy buildings is increasingly specified halogen-free. The reason is what happens in a fire: halogenated materials release hydrogen chloride, which obscures escape routes, is corrosive to people, and keeps attacking electronics and steel long after the fire is out.
Our HFFR compound is built on a base polymer chosen for filler acceptance and carries 55–65% mineral flame retardant. For compounders building their own systems, aluminium hydroxide serves polyethylene and EVA compounds processed below 200 °C, while magnesium hydroxide is stable to around 330 °C and is what polypropylene-based systems require. Zinc borate is frequently added as a char promoter, allowing a lower total mineral loading and recovering some of the mechanical properties that heavy filling costs.
The specifications that matter here are EN 60754-1 and -2 for halogen acid gas and corrosivity, EN 61034-2 for smoke density, and IEC 60332-1 or -3 for flame propagation. Passing one does not imply passing the others, which is why they are named individually.
What goes into a cable jacket?
Jacketing is a mechanical and environmental job rather than an electrical one. HDPE black compound gives hardness, abrasion resistance and low water permeability for buried and duct installation. LLDPE black trades some of that hardness for flexibility and markedly better environmental stress cracking resistance, which matters where a cable is bent tightly and then left in wet ground for years.
Both carry around 2.5% carbon black. That figure is not arbitrary: below roughly 2% ultraviolet protection falls away quickly and the jacket chalks and cracks, while above 3% the additional protection is marginal and mechanical properties suffer. Dispersion matters as much as the loading, since agglomerates leave unprotected polymer between them. Where colour coding is needed, natural HDPE and natural LLDPE are coloured at the extruder — but colour masterbatch provides no UV protection, so an outdoor coloured cable still needs a dedicated stabiliser package.
Where flexibility and flame performance have to coexist
Flexible PVC cable still accounts for a great deal of installed capacity, and the formulating problem there is balancing softness, flame performance and permanence. ESBO supports the stabiliser system while contributing flexibility; DOA brings the cold-bend performance that a general-purpose plasticiser cannot; chlorinated paraffin contributes both plasticisation and chlorine to the flame system, working with antimony trioxide as the gas-phase synergist.
How Revona supports cable manufacturers
Revona Chemicals sources and supplies these materials from its base in Istanbul, serving manufacturers in Türkiye and export markets. Technical data sheets, safety data sheets and samples are available on request, and our team can help narrow a grade selection against the standards a specific cable has to meet. Contact our technical team with the construction and the test schedule, and we will work from there.